Quick Details
Place of Origin:
Guangdong, China
Brand Name:
CPSY
Model Number:
CPY3090-30U/CPY30120-42U/CPY30120-30U
Phase:
Three Phase, 3 phase in and 3 phase out
Protection:
Unbalanced Loads
Weight:
180Kg-2850Kg
Output Voltage:
100/110/120/127/220/230VAC+/-10%
Type:
On-line
Application:
IT and industrial applications, IT or industrial
Product name:
modular ups price in pakistan
Battery Type:
Lead-acid Maintenance-free Battery
Wave Form:
Pure Sinewave
Color:
Black
Display:
LED+LCD (7inch Color Touch Screen)
MTTR:
Yes
Battery connection:
built-in or external
SNMP card:
optional
Supply Ability
Supply Ability:
1000 Piece/Pieces per Week modular ups price in pakistan
Packaging & Delivery
Packaging Details
Standard package
Port
Shenzhen
Product Description

Power system 20KVA Modular UPS with design MTTR for industrial

 

Main Features

 

High efficiency online double conversion technology

High scalability

Unity output power factor

Modular design lowers MTTR

Highly reliable operation with redundant power supply in STS

User-adjustable charging current

Ease of installation and maintenance

Flexible battery configuration adapts different applications

High overload capacity

Graphic 5.7" LCD design for easy management

N+1 or N+X parallel redundancy for power guarantee

Optional 10" touch LDC panel

 

Technical Specification

 

ModelCPY3090-30UCPY30120-42UCPY30120-30U/CPY2080-30UCPY30180-30U/CPY20120-30UCPY20200-42UCPY30240-42UCPY30300-42U
PHASE3-phase in/3 phase out
CABINET CAPACITY90KW120KW120kw / 80kw180kw/120kw200kw240kw300kw
BATTERY TYPEBuilt-in batteryExternal battery
ONE POWER MODULE CAPACITY30kva/30kw30kva/30kw or 20kva/20kw20kw30kva/30kw
MAX.POWER MODULE NO344610810
MAX.BATTERY SET NO35-----
INPUT
Nominal Voltage3 x 380vac/400vac/415vac(3Ph+N)
Voltage Range305-478vac at 100% load; 208-304vac at <70% load
Nominal Frequency50/60Hz(Auto sensing)
Frequency Range40Hz-70Hz
Power Factor>0.99 @ 100% laod, > 0.98 @ 50% load
Harmonic Distortion(THDi)<3% @ 100% load
OUTPUT
Nominal Voltage3 x 380vac/400vac/415vac(3Ph+N)
Voltage Regulation(Steady state)<±1% Typical(balanced load), <±2% Typical(unbalanced load)
Nominal Frequncy50/60Hz
Frequency Range(Synchronized)46Hz-54Hz or 56Hz-64Hz
Overload Cpacibility1 hour fpr 110%, 10mins for 125%, 1 min for 150%, 200ms for > 150%
Harmonic Distortion<2% THD(Linear load), <4% THD(Non-linear load)
EfficiencyUp to 94.5%
BATTERY/CHARGER
Nonimal Voltage+/-216v(12v x 36pcs)
Maximum Voltage+/-240v(12v x 40pcs)
Minimum voltage+/-192v(12v x 32pcs)
Float Charging Voltage2.25v/cell
Boost Charging Voltage2.35v/cell
Temperature CompensationYes
Maximum Charging Current8A8A for 30kw power module6A8A
(Per Power Module)6A for 20kw power module
PHSICAL
Cabinet Dimension(DXWXH)mm1100x600x14751100x600x20101100x600x14751100x600x14751100x600x2010
Net weight675932335/333437.5/434.5611549620
ENVIRONMENT
Operating Temperature0-40℃
Relative Humidity0-95% non-condensing
Altitude<1000m for nominal power
IP classIP20
MANEGEMENT
Smart RS-232/USBSupport Windows 2000/2003/xp/vista/2008/windows7/8, linux and mac
Optional SNMPPower management from SNMP manager and web browser
STANDARDS
SafetyIEC/EN 60950-7; IEC/EN 62040-1
EMCIEC/EN 62040-2 Category C3

 

Product Images

 

 

 

Company Information

Show you our factory and what certificates what we have

 

 

 

 

FAQ

 

What is a UPS? 
An uninterruptible power supply, also uninterruptible power source, UPS or battery/flywheel backup, is an electrical apparatus that provides emergency power to a load when the input power source, typically the utility main, fails. 
  
Why do I need a UPS? 
Power disturbances and blackouts can be costly.  Preserving Information, the availability of equipment critical to the business, maintaining fully occupied staff, reduction of cost over-runs, performing reliably and getting results on time are all key elements in any successful operation.   A UPS will provide clean, stable power to critical application equipment throughout utility power disturbances and power failure. 
  
How many types of UPS are there? 
There are three typical types of UPS: OFF-LINE, ON-LINE, and LINE INTERACTIVE. 
  
What is an " ON LINE UPS ?" 
An Online UPS takes incoming power, converts it to DC, conditions it, and converts it back to AC. This means the UPS is Online since there is no delay to switch to battery. Use an online UPS for your critical applications, high availability servers, etc. The output of these online UPS systems are TRUE sine wave, and is usually better than power from the electric company. 
  
What is a "LINE INTERACTIVE UPS ?" 
An Online UPS takes incoming power, converts it to DC, conditions it, and converts it back to AC. This means the UPS is Online since there is no delay to switch to battery. Use an online UPS for your critical applications, high availability servers, etc. The output of these online UPS systems are TRUE sine wave, and is usually better than power from the electric company. 

 

 

 